Skip to content
Product guide
Centralized Outdoor Unit

FCV042SA · FCV050SA · FCV070SA · FCV080SA · FCV085SA

Centralized Outdoor Unit

The centralized outdoor unit uses modular combinations to accurately meet different cooling-capacity requirements, with high flexibility and scalability.

Discuss this product
Features & technical specifications4 specification tables

Product features

  • Modular combinations accurately match different cooling capacity requirements, with high flexibility and scalability.
  • An integrated Refrigerant Pump free-cooling design is available, providing a highly integrated system and up to 60% footprint savings.
  • The compact base module accommodates access requirements and simplifies transportation and installation.
  • Fan motors require very little maintenance and suit a range of climatic conditions.
Centralized outdoor unit — specifications
ParameterFCV042SAFCV050SAFCV070SAFCV080SAFCV085SA
Main power supply220V 1ph 50Hz380V 3ph 50Hz380V 3ph 50Hz380V 3ph 50Hz380V 3ph 50Hz
Condenser heat-rejection capacity (kW)44.553.071.579.586.0
Outdoor fan performance
ParameterFCV042SAFCV050SAFCV070SAFCV080SAFCV085SA
Airflow (m³/h)950016000188002000022000
Fan quantity11111
Noise, sound pressure level [dB(A)]5659606162
Dimensions and weight
ParameterFCV042SAFCV050SAFCV070SAFCV080SAFCV085SA
Length (mm)8801160116011601160
Depth (mm)9801225122512251225
Height (mm)14401700202020202020
Weight (kg)150208225225240
Recommended circuit breakers and cables
ParameterFCV042SAFCV050SAFCV070SAFCV080SAFCV085SA
Circuit breaker (A)1P-10A3P-10A3P-10A3P-10A3P-10A
Cable specifications (mm²)3*1.54*1.5; 2*0.54*1.5; 2*0.54*1.5; 2*0.54*1.5; 2*0.5

Reference conditions & selection notes

  • Condenser heat-rejection capacity is determined at an outdoor ambient temperature of 35°C and a condensing-to-ambient temperature difference of 15°C.
  • Airflow is at least the rated value and is adjustable.
  • Noise values are sound pressure levels measured at rated voltage and rated power using the method specified in JB/T4330.

Precision Air Conditioning Manual, pp. 10–11