Evaporative Dry Cooler

The dry cooler is intended for projects requiring year-round water conservation. It uses air-cooled, dry-bulb heat dissipation with a typical temperature difference of 7–8°C. At a fresh-air dry-bulb temperature of 28°C, the cooling-water outlet temperature is 35°C. Wet-film evaporative cooling is required during high-temperature periods to meet annual free-cooling requirements.

Discuss this product
Features & technical specifications4 specification tables
Primary-side cold-source selection
Climate / cooling requirementWater availabilityRecommended cold source
Low ambient temperature; year-round free cooling possibleAbundantClosed or open cooling tower
Low ambient temperature; year-round free cooling possibleScarceDry cooler
High ambient temperature; mechanical-cooling backup neededAbundantChiller + cooling tower + plate heat exchanger
High ambient temperature; mechanical-cooling backup neededScarceAir-cooled chiller
Primary / secondary temperature design guidance
Design parameterPrimary sideSecondary side
Supply temperatureRecommended ≤35°C, considering local weather and required secondary supply; W45 or W+ allowed where cooling requirements permitRecommended 40–48°C for energy efficiency; temperature and flow must meet liquid-cooled component requirements
Supply / return temperature difference6–10°C; ideal 8–10°C5–10°C; recommended ideal 6–8°C
Closed tower and evaporative dry cooler comparison
Comparison itemClosed cooling towerEvaporative dry cooler
Energy efficiencyRelatively superiorRelatively inferior
FootprintSmallLarge
CostLowHigh
Annual water consumptionApproximately 1.8–2.0 L/(kW·h)<0.5 L/(kW·h); varies by city
Peak 12-hour water usageRelatively highRelatively low
Suitable regionsAbundant water resourcesWater-scarce regions; strict WUE limits
Year-round waterless operationNot possibleNot possible; water needed during high outdoor temperatures, waterless operation possible at other times
Dry-cooler source operating example
ParameterSource value
Heat-rejection basisAir-cooled / dry bulb
Typical approach Δt7–8°C
Fresh-air dry-bulb example28°C
Cooling-water outlet example35°C
Year-round free-cooling design considerationOutlet water no higher than 35°C
High-temperature operationFresh-air-side wet-film evaporative cooling required in source example

Reference conditions & selection notes

  • This source describes an evaporatively assisted dry cooler. It conserves water but is not waterless throughout the year; evaporative assistance requires water during hot weather.
  • Outlet temperature, annual water use and need for mechanical backup depend on local meteorology and operating conditions.
  • W45 and W+ are source designations; the source does not define them further.

Liquid Cooling Manual, pp. 21–23