Room-level CDU

CDU-900LF3S/D · CDU-1200LF3S/D · CDU-1800LF3S/D

Room-level CDU

Room-level CDU is a large centralized cooling unit installed separately in the air-conditioned room. It mainly consists of a cabinet, plate heat exchanger, secondary-side circulating water pump, constant-pressure liquid replenishment system, expansion tank, filters, valves, sensors, control system, display screen and power supply module. Through heat exchange via the plate heat exchanger, cooled liquid is sent to the heat source to absorb heat, and the heat-carrying liquid then re-enters the plate heat exchanger for heat exchange treatment, forming a circulating heat exchange process.

Discuss this product
Features & technical specifications1 specification table

Product features

  • Year-round free cooling capability, subject to the cold-source and operating conditions.
  • Redundant key components; anti-condensation; circulating-pump and valve self-holding; dual power supply with uninterrupted switching; liquid leakage detection.
  • Differential-pressure, flow-rate, cold-standby, hot-standby, standalone, group-control, local and remote modes; multiple units can network automatically for group management.
  • Supports mixed CPU and GPU cold-plate liquid cooling and optional standard functional modules.
  • Stepless regulation over a wide cooling-capacity and differential-pressure adjustment range.
  • Optional inlet/outlet pipe directions, filtration grades and communication protocols.
  • High-head, large-flow functionality suitable for large ring networks.
  • Internal layout for maintenance access and online automatic liquid replenishment.
  • Sanitary-grade piping with high-precision filtration.
  • RS485 serial and RJ45 Ethernet ports; Modbus, TCP and UDP protocols.
Room-level CDU model specifications
MODELCDU-900LF3S/DCDU-1200LF3S/DCDU-1800LF3S/D
Rated heat exchange capacity (kW)90012001800
Unit rated flow rate (L/min)133017202400
Pump typeSingle pump / Dual pumpSingle pump / Dual pumpSingle pump / Dual pump
Primary supply/return fluid temperature (°C)35/4535/4535/45
Primary working fluidSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solution
Secondary supply/return fluid temperature (°C)40/5040/5040/50
Secondary working fluidSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solution
Dimensions W × D × H (mm)950x1500x22001200x1800x22001200x2000x2200
Power supply specificationsPower supply: 2-way 3Ph AC380-415V 50HzPower supply: 2-way 3Ph AC380-415V 50HzPower supply: 2-way 3Ph AC380-415V 50Hz
Dual power input (optional)Supported power sources: Mains / UPS / Diesel generatorSupported power sources: Mains / UPS / Diesel generatorSupported power sources: Mains / UPS / Diesel generator
Storage environment temperature and humidityStorage environment temperature and humidity: -45~85℃; 5%~85% RH non-condensing (long-term), 5%~95% RH non-condensing (short-term)Storage environment temperature and humidity: -45~85℃; 5%~85% RH non-condensing (long-term), 5%~95% RH non-condensing (short-term)Storage environment temperature and humidity: -45~85℃; 5%~85% RH non-condensing (long-term), 5%~95% RH non-condensing (short-term)
AltitudeAltitude: 3000m (derated above 3000m; ambient temperature rating decreases by1.5℃ for every 200m increase in altitude)Altitude: 3000m (derated above 3000m; ambient temperature rating decreases by1.5℃ for every 200m increase in altitude)Altitude: 3000m (derated above 3000m; ambient temperature rating decreases by1.5℃ for every 200m increase in altitude)

Applications

High-density data centers · Retrofit and new-build data centers · Intelligent computing centers · Large-scale computer rooms · AI training clusters · High-power industrial equipment cooling · Scientific research laboratories

Reference conditions & selection notes

  • Verify ratings for the selected coolant and operating conditions. Storage humidity is non-condensing; altitude derating applies above 3000 m at 1.5°C per additional 200 m.

Liquid Cooling Manual, p. 3