Row-level CDU

CDU-300LL3S · CDU-600LL3S · CDU-300LL3D · CDU-600LL3D

Row-level CDU

The row-level CDU is a large centralized cooling unit installed side-by-side with server cabinets. It mainly consists of a cabinet, plate heat exchanger, secondary-side circulating water pump, constant-pressure liquid replenishment system, expansion tank, filters, valves, sensors, control system, display screen and power supply module. Through the plate heat exchanger, cooled liquid is sent to the heat source to absorb heat, and the heat-carrying liquid then re-enters the plate heat exchanger for heat exchange treatment, forming a circulating heat exchange process.

Discuss this product
Features & technical specifications1 specification table

Product features

  • Dual power supply backup
  • High-efficiency variable-frequency single pump or dual pump optional
  • Anti-condensation control
  • Optional 50μm ultra-fine filtration unit
  • Automatic liquid replenishment system
  • Online maintenance
  • Intelligent group control
  • Corrosion-resistant stainless steel piping
  • Intelligent monitoring system
  • Online water quality monitoring
  • 10%–100% adjustable flow rate
  • Overpressure protection
  • Low energy consumption design
  • Leakage detection function
  • 10-inch color display screen
CDU internal equipment arrangement and heat-exchange circuit.
CDU internal equipment arrangement and heat-exchange circuit.
Row-level CDU model specifications
MODELCDU-300LL3SCDU-600LL3SCDU-300LL3DCDU-600LL3D
Rated heat exchange capacity (kW)300600300600
Unit rated flow rate (L/min)470860470860
Pump typeSingle pumpSingle pumpDual pumpDual pump
Primary supply/return water temperature (°C)35/4535/4535/4535/45
Primary working fluidSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solutionSoftened water, PG25 aqueous solution, EG25 aqueous solution
Secondary supply/return water temperature (°C)40/5040/5040/5040/50
Secondary working fluidPG25 aqueous solution, EG25 aqueous solutionPG25 aqueous solution, EG25 aqueous solutionPG25 aqueous solution, EG25 aqueous solutionPG25 aqueous solution, EG25 aqueous solution
Dimensions W × D × H (mm)600*1200*2200600*1400*2200600*1200*2200900*1400*2200
Power supply specifications2-way 3Ph AC380-415V 50Hz2-way 3Ph AC380-415V 50Hz2-way 3Ph AC380-415V 50Hz2-way 3Ph AC380-415V 50Hz
Dual power input (optional)Mains / UPS / Diesel generator power supplyMains / UPS / Diesel generator power supplyMains / UPS / Diesel generator power supplyMains / UPS / Diesel generator power supply
Storage environment temperature and humidity-45 ~ 85℃; long-term 5%~85% non-condensing, short-term 5%~95% non-condensing-45 ~ 85℃; long-term 5%~85% non-condensing, short-term 5%~95% non-condensing-45 ~ 85℃; long-term 5%~85% non-condensing, short-term 5%~95% non-condensing-45 ~ 85℃; long-term 5%~85% non-condensing, short-term 5%~95% non-condensing
Altitude3000m (above 3000m, derated; for every 200m increase in altitude, ambient temperature rating decreases by 1.5℃)3000m (above 3000m, derated; for every 200m increase in altitude, ambient temperature rating decreases by 1.5℃)3000m (above 3000m, derated; for every 200m increase in altitude, ambient temperature rating decreases by 1.5℃)3000m (above 3000m, derated; for every 200m increase in altitude, ambient temperature rating decreases by 1.5℃)

Applications

High-density data centers · Retrofit and new-build data centers · Intelligent computing centers · Large-scale computer rooms · AI training clusters · High-power industrial equipment cooling · Scientific research laboratories

Reference conditions & selection notes

  • The source states that the above ratings are based on pure water as the working medium. Confirm cooling capacity and fluid requirements with technical personnel; the matrix also lists glycol options.
  • Storage humidity values are non-condensing. Above 3000 m, the ambient temperature rating decreases by 1.5°C for each additional 200 m.

Liquid Cooling Manual, pp. 1–2