Cabinet-mounted Air-to-Liquid CDU

Cabinet-mounted Air-to-Liquid CDU is designed specifically for high heat density liquid-cooled server application scenarios. It requires no external cooling water supply or overhead cabling via raised floor systems. The overall cooling system layout is simple, with a short installation cycle and easy operation and maintenance. It is particularly suitable for retrofitting traditional air-cooled data centers and small high-performance computing centers.

How it works

The cabinet-mounted air-to-liquid CDU consists of rear fans, high-efficiency air-to-liquid heat exchangers, water pumps, controllers and pipeline components. Driven by the water pump, high-temperature working fluid from liquid-cooled servers undergoes convective heat exchange with cold air in the data room. After cooling, the fluid returns to the liquid-cooled servers to complete the heat exchange cycle.

Discuss this product
Features & technical specifications2 specification tables

Product features

  • Single-cabinet heat exchange capacity up to 120 kW
  • Rapid deployment
  • Two high-performance water pumps
  • Integrated control system supporting mainstream communication protocols
  • N+1 high-efficiency hot-swappable fans
  • Total power consumption below 5% of heat load
  • Compatible with existing hot and cold aisle layouts
CDU-16AJ model specifications
MODELCDU-16AJ
Heat exchange capacity (kW)16
Primary side inlet air temperature (°C)25
Air volume (m³/h)2700
Secondary side liquid supply temperature (°C)40
Secondary side working fluidPG25
Secondary side flow rate (L/min)25
Secondary side filtration precision100μm
Secondary side connection type1.5" tri-clamp
Circulating pump quantityDual pumps
Dimensions W × D × H (mm)482*857*443
Power supply specifications220V/50Hz
CDU-120AL3SS61222 model specifications
MODELCDU-120AL3SS61222
Heat exchange capacity (kW)120
Primary air inlet temperature (°C)24
Airflow rate (m³/h)15000
Secondary fluid inlet temperature (°C)≤ 45
Secondary filtration precision (mesh)100
Secondary interface sizeDN50
Circulating pump quantity2
Dimensions W × D × H (mm)600*1200*2200
Power supply specifications380V/50Hz
Power consumption (kW)<5

Reference conditions & selection notes

  • Both model tables appear on slide 5 with the cabinet-mounted air-to-liquid description. They are preserved separately; the source does not explicitly map every cabinet feature to both models.
  • Cooling capacity depends on working conditions. Confirm the selected working conditions and cooling medium with technical personnel.
  • CDU-16AJ filtration is 100 μm; CDU-120AL3SS61222 filtration is 100 mesh. These are different source units and are not interchangeable.
  • The 120 kW model lists <5 kW consumption; the description separately states total power below 5% of the heat load. These apply to the specified operating point, not every load.

Liquid Cooling Manual, p. 5