Liquid-Cooled Door

Active Type · Passive Type

Liquid-Cooled Door

Installed at the cabinet rear or front to enhance server airflow, the liquid-cooled door can combine with cold-plate cooling for a fully liquid-cooled cabinet. It is intended for high cabinet heat loads and equipment sensitive to ambient temperature. The active rear-door version comprises a heat exchanger, fan wall and sheet-metal components; the passive version comprises a heat exchanger and perforated door.

Discuss this product
Features & technical specifications1 specification table

Product features

  • Self-diagnosis and on-site diagnosis
  • Safety protection and leakage detection
  • HMI displaying alarm information
  • Standard quick couplings
  • Bottom casters for door movement and rapid deployment
  • Modular design for different data-center scales and layouts
Active and passive liquid-cooled door specifications
ParameterActive TypePassive Type
Power supplyAC220VDC48V
Output CapacityCooling Capacity:20kW @AT=2.7℃, 130L/minCooling Capacity:10.1kW @AT=2.6℃, 55L/min
Water-side supply / return temperature32/34.2℃32/34.7℃
Air-side inlet / outlet temperature45℃/34.7℃40℃/34.6℃
Water Flow Rate130L/min55L/min
Airflow Rate6300 m³/h5950 m³/h
Liquid-Cooled Door Water-Side Pressure Drop74.2KPa43KPa
Power consumption1.1kW30W
Dimensions W × D × H595×250×2250 mm599.5*150*2195mm
Net / operating weight105kg/115kg71.5kg/91.5kg
Compatible cabinet W × D × H600*1200*2250mm600×1200×2200mm

Applications

High-density data centers · Edge computing nodes · Special industry scenarios · Legacy data center renovation scenarios

Reference conditions & selection notes

  • Capacity is stated at the individual source duty points: active 20 kW at AT=2.7°C and 130 L/min; passive 10.1 kW at AT=2.6°C and 55 L/min. The source does not define AT, so it is not relabeled as another temperature difference.
  • The water temperatures, airflow, pressure drops, power, dimensions and compatible cabinet dimensions are separate for active and passive versions.
  • Slide 20 shows cold plate + liquid-cooled rear door as an all-liquid architecture option. Compressor-free operation depends on cold-source conditions and permissible cabinet inlet-air temperature.

Liquid Cooling Manual, p. 8