Liquid Cooling Temperature Control System

System integration and controls

Liquid Cooling Temperature Control System

The temperature-control system connects the external cold source, primary-side pipework, CDU and controls, secondary-side pipework and server distribution. The distributed cold-plate arrangement includes a cold source, rack-mounted CDU, primary-side pipelines, cooling medium, liquid-cooled cabinet, liquid distributor, fluid connectors, cold plates, hydraulic hose assemblies and liquid-cooled backplanes. Immersion systems add a tank or cabinet, fluid replenishment and solution recovery. Selection starts with the server heat load, required inlet-fluid conditions and permitted pressure drop.

How it works

In a cold-plate circuit, the circulating pump supplies cooled secondary fluid to the server cold plates. The coolant absorbs component heat and returns through the distribution unit and secondary pipework to the CDU plate heat exchanger. The primary circuit transfers that heat to a cooling tower, dry cooler or chiller. The air-cooling channel removes remaining server heat through IDEC, DPC, a coil air wall, a liquid-cooled door or another suitable air system. In immersion cooling, the source distinguishes single-phase and phase-change server/tank arrangements.

Discuss this product
Features & technical specifications10 specification tables

Product features

  • Temperature-control functional tests include supply-liquid temperature, differential pressure and temperature regulation.
  • Dual-pump switching, make-up pump start/stop and circulation-pump operation control.
  • Automatic fluid make-up, liquid-leakage detection and anti-condensation control.
  • Manual control; automatic restart after power recovery; dual-power-supply switching.
  • Conductivity alarm setpoint configuration.
  • Main-loop supply / return differential-pressure control.
  • Main-loop supply-liquid temperature control.
  • Control based on the hydraulically most unfavorable loop.
Cold source and CDU heat-exchange circuit, with cold-plate and immersion heat-removal paths.
Cold source and CDU heat-exchange circuit, with cold-plate and immersion heat-removal paths.
Liquid-cooling technology routes
Heat-transfer routeTechnologySource-described equipment arrangement
IndirectCold-plate liquid coolingRack-mounted, cabinet-mounted or large CDU; air/liquid or liquid/liquid heat exchange as illustrated
DirectSpray liquid coolingDirect liquid-cooling route in source roadmap
DirectSingle-phase immersion liquid coolingImmersion tank; liquid/liquid heat exchange
DirectPhase-change immersion liquid coolingPhase-change immersion tank; liquid/liquid heat exchange
Temperature-control product coverage
No.CategorySource-defined equipment
1Cold sourceAbundant water: cooling tower; scarce water: evaporative dry cooler; special scenarios: chiller
2Primary-side pipelinePrimary-side pipeline and construction
3CDUCDU and control system
4Secondary-side pipelineSecondary-side pipeline and construction
5DistributionManifold
6ImmersionImmersion tank
Server-side design information required
Design inputSource requirement
Heat loadServer power and proportion of heat removed by liquid cooling
Liquid temperatureRequired inlet temperature and permitted temperature range
Wetted connectionsMaterial requirements for inlet / outlet connections
HydraulicsInternal server pressure drop, pressure-bearing capacity and inlet flow
External connectionInterface specification and model
Air channelServer air inlet and outlet temperatures
Cold-plate and immersion system scope
ArchitectureSource equipment scope
Cold plateDry / evaporative full free-cooling cold source; centralized / distributed temperature-control unit; prefabricated clean network and distribution unit; standard liquid-cooled cabinet with intelligent control
ImmersionDry / evaporative full free-cooling cold source; centralized / distributed temperature-control unit; immersion tank / cabinet and prefabricated pipe network; fluid replenishment, solution recovery and intelligent control
Combined air and liquid heat-removal architecture
ChannelSource-described share of server heatCooling arrangement
Liquid50–90%Direct CPU liquid cooling; source describes liquid-cooled servers with built-in heat-pipe heat-exchange modules
Air10–50%IDEC, DPC, coil air wall, liquid-cooled door or other air-side technology; chilled-water or refrigerant-based cold source
Air-side integration options
Cold-plate combinationAir-side cold source / condition
Coil air wallChilled water or refrigerant-based system
IDECShown as a combined architecture; source slide supplies no individual performance rating
Liquid-cooled rear doorChilled water; high-temperature water possible if cabinet permits high-temperature inlet air
Terminator air wallChilled water or refrigerant-based system
All-liquid extensionSource states compressor mechanical refrigeration may be avoided; depends on permissible inlet conditions and cold source
Distributed cold-plate source performance statements
ItemSource statement (slide 1)
Single-point heat dissipationExceeds 700 W
Cabinet densityCan increase by 50%
PUE<1.1
Reliability designN+1; three-level anti-leakage design; liquid separated from electronic components
Chip temperature comparison20–30Β°C below the cited air-cooling comparison; source describes longer equipment life and support for overclocking
Noise comparisonMore than 30 dB reduction versus the cited air-cooled comparison
DeploymentFactory manufacturing, assembly and testing; on-site pipeline/cable connections; modular deployment
Technology overview reference statements
ItemSource reference statement (image-only slide 13)
Liquid volumetric heat capacity relative to air1000–3500 times
Thermal conductivity relative to air20–30 times
Precision coolingComponent-level cooling
PUE reference range1.05–1.2
Noise referenceAs low as 50 dB with no compressor and no or low-speed fans
Space reference50–80% space savings through increased cabinet density
Technology distinctionIndirect cold-plate cooling; direct single-phase or phase-change immersion cooling
Third-party cold-plate schematic reference
ParameterSugon reference illustration (image-only slide 14)
Server / internal-circuit supply water40–55Β°C
Server / internal-circuit return water50–65Β°C
Outer-circuit supply water35–50Β°C
Outer-circuit return water45–60Β°C
Liquid-section PUE reference<1.1
Air / liquid hybrid PUE reference<1.2
Reference flow pathCold plates β†’ horizontal distribution manifold β†’ vertical distribution manifold (VCDU) β†’ CDU heat exchanger / pump β†’ closed cooling tower (compressor-free in schematic)
Control functions and granularity
CategorySource function
Functional testsSupply-fluid temperature, differential pressure and temperature-regulation test
Pump functionsDual-pump changeover, make-up pump start / stop, circulation-pump operation
Fluid protectionAutomatic make-up, leakage detection, anti-condensation
Operating modesManual operation and auto-restart after power recovery
PowerDual-power-supply changeover
Water qualityConductivity alarm setpoint
Loop controlSupply / return differential pressure in main loop
Temperature controlMain-loop supply-fluid temperature
Hydraulic coverageMost unfavorable loop control

Applications

Cold-plate liquid-cooled data centers Β· Immersion liquid-cooled data centers Β· Retrofits requiring a combined air and liquid heat-removal architecture Β· Intelligent computing and AI clusters Β· Retrofitted data centers with increased capacity Β· Small-scale computing centers and small computer rooms Β· Small and micro AI training clusters Β· High-power-density equipment and research laboratories

Reference conditions & selection notes

  • Image-only slides 13 and 14 contain technical content. Slide 14 is explicitly a Sugon reference schematic; its temperatures and PUE values are not Cooltechx product ratings or promises.
  • The slide 1 distributed-system claims (>700 W per point, PUE <1.1, +50% cabinet density, 20–30Β°C chip-temperature reduction and >30 dB noise reduction) lack a defined test boundary in the source. They are reference statements requiring project confirmation; the source phrase near-zero leakage risk is a design claim rather than a quantified guarantee.
  • Slide 13 claims broad year-round natural cooling and cites PUE 1.05–1.2, 50 dB noise and 50–80% space savings without fluid, climate or load conditions. These are technology-overview examples, not universal outcomes.
  • PUE values have different source scopes: distributed cold plate <1.1 on slide 1; overview 1.05–1.2 on slide 13; Sugon liquid section <1.1 and hybrid <1.2 on slide 14; ACM system ≀1.13 on slide 25. They must not be combined into one guaranteed rating.
  • The liquid share of 50–90% and air share of 10–50% are architectural guidance; select the heat split from the actual server. The server inlet temperature, pressure and material requirements govern the final design.
  • The source uses the term heat-pipe heat-exchange modules on slide 18; it is retained as source wording and does not establish the construction of every compatible server.
  • The source overview names free-cooling cold sources for cold-plate and immersion systems. Annual availability and compressor-free operation require assessment of weather, water resources, server temperature limits and the remaining air-side cooling load.

Liquid Cooling Manual, pp. 1 and 12–20, 24, 28 and 33; pp. 13–14 include reference illustrations